1 Ordering Code
APC-SV8 - Eight Position Step Control with Vernier
APC-SV4 - Four Position Step Control with Vernier

2 Description
The APC-SV8 is a microcontroller-based step controller that provides precise modulation in multi-stage heater applications such as duct heaters. The built-in Vernier stage allows for smooth, precision control of the load without increasing switching wear.

3 Key Features

  • Adjustable Stage Delay

  • Pulsed or Analog Vernier Output

  • Adjustable Vernier Ratio

  • Expandable to 16 stages

  • LIFO/FIFO Selection

  • Test Button

  • Brown Out Protection

4 Installation

WARNING: FIRE HAZARD!!  Even quality electronic components CAN FAIL KEEPING FULL POWER ON!  Provide a SEPARATE (redundant) OVER TEMPERATURE SHUTDOWN DEVICE to switch the power off if safe temperatures are exceeded.

WARNING: HIGH VOLTAGE!!  This control is wired to a transformer, Solid State Relay, and contactors with high voltage on them. This control must be installed in a GROUNDED enclosure by a qualified electrician in accordance with applicable local and national codes including NEC and other applicable codes. Provide a safety interlock on the door to remove power before gaining access to the device.

4.1 Mounting Instructions/Dimensions

The APC-SV8 should be mounted using #6 screws at the five locations shown below. The board is supported by 5, 5/16" high spacers (supplied).

5 Dipswitch Settings

5.1 Input Selection

S1 positions 1-5, select which command input the APC-SV8 will accept.

OFF

Switch S1

Command Input

Pos 1

Pos 2

Pos 3

Pos 4

Pos 5

0-5V

0-10V*

2-10V*

4-20mA

0-135 OHM

mA

mA

10V

135R

135R

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

ON

ON

ON

ON

ON

ON

ON

*If the 0-10V range is selected, the APC-SV8 will start responding with output just above 0V on the command input. If the 2-10V range is selected, the APC-SV8 will start responding with output just above 2V on the command input.

5.2 Stage Selection

S2 positions 1-4 select the number of output stages.

Switch S2

Output Stages

Pos 1

Pos 2

Pos 3

Pos 4

1

2

3

4

5

STP3

STP2

STP1

STP0

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

ON

ON

ON

ON

ON

6

7

8

9

10

11

12

13

14

15

16

OFF

ON

ON

OFF

OFF

ON

ON

OFF

OFF

OFF

ON

ON

ON

ON

OFF

OFF

OFF

ON

ON

OFF

OFF

ON

ON

OFF

OFF

ON

ON

ON

OFF

ON

ON

OFF

OFF

ON

ON

ON

OFF

ON

ON

ON

ON

ON

ON

ON

OFF

5.3 Output Mode Selection

LIFO (last in first out) and FIFO (first in first out) modes are both available by setting of S2 position 6.  

LIFO/FIFO

SWITCH S2

Pos 6

LIFO

FIFO

FIFO

OFF

ON

LIFO mode is the normal default mode. In this mode the output stages respond like a level bar graph.

FIFO mode circulates the on stages to promote even use of the contactors and elements. For example, the first stage that was turned on when the power was increasing will be the first stage turned off when the power is decreasing.

5.4 Master/Slave Selection

S2 positions 5 selects master or slave operation.

Master/Slave

SWITCH S2

Pos 5

MASTER

SLAVE

SLV

OFF

ON

LIFO mode is the normal default mode. In this mode the output stages respond like a level bar graph.

FIFO mode circulates the on stages to promote even use of the contactors and elements. For example, the first stage that was turned on when the power was increasing will be the first stage turned off when the power is decreasing.