10-50AMP Rated
"COOL ONE" Top Mount Current Transformer Assembly

Functions as a load monitor for currents up to 50A  AC.  Current Transformer circuitry provides for either 0-50 ma ac or 0-10 volts dc, adjustable from a multi turn pot.  The Current Transformer provides 1ma per amp.  Assembly mounts on top of any solid state relay via press-on adaptor which also provides touch safe feature for active high voltage terminal of relay and allows the relay assemblies to be mounted side by side to save space.

APC7130 SSR Assembly
w/ APC5048CT Mounted

Standard Cool One Features:

  • 0-10Vdc signal proportional input amps

  • Output voltage pot adjustable from 10 to 50Amps

  • Over voltage zener protected to 15Vdc

  • CT output 1ma/A

  • Attaches to all standard Hockey Puck Style SSR's

  • 2 3/16" Snap Track Mountable

  • Small outline maintains SSR DIN side by side mounting

The APC5048CT provides an adjustable DC voltage when a lead from relay output terminal is passed through the CT opening to the load. The output can be scaled by adjusting the trim pot "P1" which is provided on the APC5048CT. This will allow the user to achieve a 0-10Vdc full scale for any current from 10A to 50A.

See Connection Diagrams

APC5048CT
Current Transformer Module

PART NUMBER

LINE

CURRENT

CT OUTPUT

LINE

VOLTAGE

TRANSIENT VOLTAGE

RELAY TYPE

APC5048CT

10-50Amps AC

Zener Protected to 15Vdc Max

1ma AC per Amp or 0-10Vdc

24-660Vac

Zero Cross or RTO

MECHANICAL DRAWING

CT BOARD SCHEMATIC

CONNECTION DIAGRAMS

NOTES:

The APC5048CT can be used to monitor load currents lower than 10Amps by following the equation:
A x (1+T) = 10. Where A= Load Current and T = the number of loops through the APC5048CT.

For example, if A= 3Amps and T = 3, then 3 x (1+3) = 12.

In this example, three loops around the CT will make the 3Amps look like 12Amps to the APC5048CT. The result will meet the minimum value necessary to adjust the pot "P1" to 10Vdc full scale.

bottom of page