25A/Leg 3 Phase SCR Controller
[2 Leg Break, 3 Phase]
"COOL ONE" Duct Mount 2 Leg Break Burst Fire SCR Controller
Anacon Power & Controls SCR Controller's are designed to offer proven solutions to both Phase Angle and Burst Fire applications. Our Burst Fire SCR Controllers operate by varying the duty cycle of an SSR's control input. The power delivered to the load is proportional to the command input signal from four selectable time bases. (200ms, 1 sec, 10 sec & 100 sec.) SCR Controllers allow you to apply more precise control to any heater application, regardless of the type of heater elements you choose.
Standard Cool One Features:
-
Current Ratings from 0.1A/Leg to 25A/Leg
-
Standard LED Status Indicator
-
UL/cUL Recognized TUV Approved & CE Compliant Version
-
Input Option: 4-20mA, 0-10V, 0-5V, 0-135Ω, Potentiometer
-
Built in Transient Protection
-
Configurable for 4 different cycle times
-
Limited 2 Year Warranty
-
Line Voltage to 660 Vac.
-
See User Manual for complete list of commands & wiring options.
SPECIFICATIONS
PART NUMBER
INPUT
RANGE
ASSEMBLY LOAD CURRENT
(AMPS AC)
LINE
VOLTAGE
PEAK VOLTAGE
RELAY RATING
APCSCR25DPHLZ
4-20mA, 0-10Vdc, 0-5Vdc,
0-135Ω , Potentiometer
1200V Peak
.1A/Leg-25A/Leg Max @
40C Ambient
48-660Vac
25A/Leg
APCSCR25DDHLZ
4-20mA, 0-10Vdc, 0-5Vdc,
0-135Ω , Potentiometer
.1A/Leg-25A/Leg Max @
40C Ambient
48-660Vac
1200V Peak
25A/Leg
Notes:
-
Ratings based upon 100% duty cycle for 20 minutes or 80% duty cycle continuous.
-
Ratings are based upon relays being mounted either individually or side by side with zero spacing.
-
Cool One's unique construction allows better performance than conventional heat sink designs even when mounted side by side.
MECHANICAL DRAWING
THERMAL CURVE
MOUNTING DIAGRAM
CYCLE TIME
4
6
COMMAND INPUT
1
2
3
5
0-5V (Default)
Potentiometer
0-10V
4-20Ma
1-5V
2-10V
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
On
Off
Off
Off
On
On
On
On
On
Off
Off
Off
Off
Off
0-135Ω*
On
Off
Off
Off
100 Seconds
*Module must be ordered as APCSCR1Z-135 for 0-135Ω input support.
0-135Ω input support is only usable with 24VAC Power.
​